Motor Starting Auto Transformer

Technical Data

Capacity

  • single tapping @ 70%
  • three tapping @ 50%, 60% and 75%

E-I silicon steel grade

  • 0.5mm silicon steel

Cooling

  • natural air

Cool safety

  • thermostat protected for transformer above 11KW

Termination of wires

  • high quality nylon terminal block
  • chrome steel metal bolts & nuts

Re-start frequencies

  • maximum re-start frequencies of 8 times per hour at appropriate intervals

Insulation class

  • class F

Optional

  • customize designs are available upon request

Technical Specification for Aluminium Wire

capacity
(kw)
hp thermostat no. of tapping tapping
percentage
mounting pitch (mm)
x             y
overall dimensions (mm)
w           d           h
weight
(kg)
3.75 5.0 nil/1 single 70% 120         185 215      195      90 5.5
5.5 7.5 nil/1 single 70% 120         185 215      195      95 6.5
7.5 10 nil/1 single 70% 120         185 215      195     100 7.0
11 (S) 15 nil/1 single 70% 140         210 240      215     100 9.5
11 3T 15 1 three 50% 60% 75% 140         210 240      225     140 9.6
15 20 1 three 50% 60% 75% 140         210 240      225     155 11.5
22 30 1 three 50% 60% 75% 155         240 270      245     155 15.0
30 40 1 three 50% 60% 75% 155         240 270      245     160 16.5
37.5 50 1 three 50% 60% 75% 155         240 300      275     170 19.0
45 60 1 three 50% 60% 75% 185         270 300      275     170 20.5
56 75 1 three 50% 60% 75% 185         270 300      275     180 25.5
66 88 1 three 50% 60% 75% 185         270 300      275     210 34.0
80 107 1 three 50% 60% 75% 210         305 340      300     205 36.0
94 125 1 three 50% 60% 75% 210         305 340      300     215 41.0
110 150 1 three 50% 60% 75% 220        305 340      310     245 56.0
132 175 1 three 50% 60% 75% 220         305 340      310     245 61.0
150 200 3 three 50% 60% 75% 210         170 360      370     390 91.0
180 240 3 three 50% 60% 75% 260         170 410      380     400 105.0
225 300 3 three 50% 60% 75% 260         190 410      400     400 120.0

Technical Specification for Copper Wire

capacity
(kw)
hp thermostat no. of tapping tapping
percentage
mounting pitch (mm)
x             y
overall dimensions (mm)
w           d           h
weight
(kg)
3.75 5.0 nil/1 single 70% 120         185 215      195      90 6.1
5.5 7.5 nil/1 single 70% 120         185 215      195      95 7.5
7.5 10.0 nil/1 single 70% 120         185 215      195     100 8.6
11 15 nil/1 single 70% 140         210 240      215     100 10.7
11 15 1 three 50% 60% 75% 140         210 240      225     145 12.4
15 20 1 three 50% 60% 75% 140         210 240      225     155 13.9
22 30 1 three 50% 60% 75% 155         240 270      245     150 17.3
30 40 1 three 50% 60% 75% 155         240 270      245     155 19.3
37.5 50 1 three 50% 60% 75% 155         240 270      245     155 21.1
45 60 1 three 50% 60% 75% 185         270 300      275     160 24.0
56 75 1 three 50% 60% 75% 185         270 300      275     180 30.3
66 88 1 three 50% 60% 75% 185         270 300      275     190 35.1
80 107 1 three 50% 60% 75% 210         305 340      300     210 42.3
94 125 1 three 50% 60% 75% 210         305 340      300     215 48.3
110 150 1 three 50% 60% 75% 220         305 340      310     235 62.5
132 175 1 three 50% 60% 75% 220         305 340      310     245 68.8
150 200 3 three 50% 60% 75% 210         170 360      370     390 100
180 240 3 three 50% 60% 75% 210         180 360      380     390 115
225 300 3 three 50% 60% 75% 210         190 360      390     390 130